Chapter 2 Installation & Wiring
• The earth ground terminal of the E3 Overload Relay shall be connected to
a solid earth ground via a low-impedance connection.
• Installations employing an external ground fault sensor shall ground the
cable shield at the sensor with no connection made at the E3 Plus Overload
Relay.
• The PTC thermistor cable shield shall be grounded at the E3 Plus
Overload Relay with no connection made at the opposite end.
Short-Circuit Ratings
The E3 Overload Relay is suitable for use on circuits capable of delivering not
more than the RMS symmetrical amperes listed in the following tables.
Short-Circuit Ratings
Table 10 - UL
Table 11 - IEC
Cat. No.
Maximum
193-EC_ _ 592-EC_ _ Available Fault Current [A] Voltage [V]
B
T
5,000
600
D
C
E
D
10,000
F
G
18,000
H
42,000
Z
5,000
Cat. No.
Prospective
Current I
r
[A]
Conditional Short-Circuit
Current I
q
[A]
193-EC_ _ 592-EC_ _
Maximum Voltage [V]
B
T
1,000
100,000
690
D
C
3,000
E
D
5,000