Select ok, Correct the fault input to the aux out 5, Do one of the following – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual
Page 128: When the download is successful, select ok

128
Rockwell Automation Publication 825-UM004D-EN-P - November 2012
Chapter 9 825-PDN DeviceNet Communication Card
28.
Select OK.
29.
Moving cursor into the grid, place Aux Out 5 to the right of the AND
function block
30.
Correct the Fault Input to the Aux Out 5.
31.
Do one of the following:
•
In the toolbar, select Tools.
•
From the pull-down menu, select Logic Verify.
32.
To toggle out of edit mode if you are online with a device, select Tools.
33.
After selecting Edit from the main menu, select Download from the pull-
down menu (right corner of the toolbar).
34.
When the download is successful, select OK.
35.
From the same pull-down menu, select Logic Enable On.
36.
The 825-P Modular Protection System is now programmed and the logic
is active.
NOTE:
The PLC key switch must be in the Program position. If not, the download does not occur and
a generated error occurs.