Testing & Troubleshooting Chapter 11
Power and Power Factor Measuring Accuracy
The following tests assume use of an MCM2, MCM5, or MCM20 converter
module.
Wye-Connected Voltages
Perform the following steps to test wye-connected voltages:
1.
Connect the current source to the MCM module, as shown in Figure 50.
2.
Connect the voltage source to the 825-P, as shown in Figure 51. Make sure
that Xfmt Connection = Wye.
Figure 51 - Wye Voltage Source Connections
3.
Using the front panel SET/SHOW or MPS Explorer software, record the
Phase CT Ratio, Phase VT Ratio, and Phase Rotation setting values.
4.
Apply the current and voltage quantities shown in Column 1 of Table 87.
Values are given for Phase Rotation = ABC and Phase Rotation = ACB.
5.
Use the front panel METER function or MPS Explorer software to verify
the results.
|IA| = FLA
12%
|IB| = 1.2 • FLA
|IC| = 1.2 • FLA
|IA| = 0.9 • FLA
13%
|IB| = 1.1 • FLA
|IC| = 1.1 • FLA
Table 86 - Current Unbalance Measuring Accuracy
|I| Applied (A secondary)
Expected Reading (%)
Actual Reading (%)
825-P
L1
L2
L3
N
Voltage
Test
Source
VA
VB
VC
VN