DeviceNet Information Chapter E
Instance 4 is the Predefined Group 2 Connection Set Change of State/Cyclic IO
Message Connection. The following Instance 4 attributes are supported:
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
State
USINT
0 = nonexistant
1 = configuring
3 = established
4 = timed out
2
Get
Instance Type
USINT
1 = I/O Connection
3
Get
Transport Class Trigger
USINT
0x00 (Cyclic, unacknowledged)
0x03 (Cyclic, acknowledged)
0x10 (COS, unacknowledged)
0x13 (COS, acknowledged)
4
Get
Produced Connection ID
UINT
01101xxxxxx
xxxxxx = node address
5
Get
Consumed Connection ID
UINT
10xxxxxx101
xxxxxx = node address
6
Get
Initial Comm Characteristics
USINT
0x02 (acknowledged)
0x0F (unacknowledged)
7
Get
Produced Connection Size
UINT
0 to 8
8
Get
Consumed Connection Size
UINT
0 to 8
9
Get/Set
Expected Packet Rate
UINT
in milliseconds
12
Get
Watchdog Action
USINT
0 = transition to timed out
1 = auto delete
2 = auto reset
13
Get
Produced Connection Path Length
UINT
8
14
Get
Produced Connection Path
21 04 00 25 (assy inst #) 00 30
03
15
Get
Consumed Connection Path Length
UINT
8
16
Get/Set
Consumed Connection Path
21 04 00 25 (assy inst #) 00 30
03