Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual
Page 46

46
Rockwell Automation Publication 825-UM004D-EN-P - November 2012
Chapter 4 Hardware Commissioning
•
Select Yes to confirm the new hardware configuration, and the display
will show:
•
Press Enter to reboot the relay.
•
If existing configuration parameters are not proper for the specific
hardware configuration, then the following message will be displayed
•
To correct the configuration parameters reset the relay to the default
parameters for the specific hardware configuration by navigating to Main-
>Reboot/Restore and select Restore Defaults in which the following
display will appear:
•
Select Yes and the relay will reboot. With the updated configuration
parameters, the display will show the following error message:
•
Navigate to Main > Status to view the Status display
•
The display will show the following message:
Config Accepted
Enter to Reboot
Setting Mismatch
Adjust Settings
Restore Default
No Yes
STATUS FAIL
MCM/CWE Error
Confirm Hardware
Config (Enter)