Chapter 10 Modbus RTU Communications
Figure 47 - Example of Modbus network consisting of a MicroLogix 1500 PLC as the Master device
and an 825-P and PanelView 550 as the Slave devices.
Commissioning
The Modbus communication card (Port 4) can be configured through
the front panel or serial port using the following settings. Front panel
access uses the following path:
MAIN > Set/Show > Port > Port 4
Table 63 - Modbus communication card settings
The following table provides settings to use for each communication card:
Table 64 - Communication card settings
Setting Prompt
Setting Range
Factory Default
COMM INTERFACE
232, 485
232
PROTOCOL
ASC, MOD
MOD
SPEED
300 … 38,400 bps
19,200
PARITY
O, E, N
N
MODBUS SLAVE ID
1 … 248
248
Setting Prompt
Setting Range
DeviceNet
Modbus
Empty
COMM INTERFACE
232, 485
232
232
232
PROTOCOL
ASC, MOD
MOD
MOD
MOD
SPEED
300 … 38,400 bps
19,200
19,200
19,200
PARITY
O, E, N
N
N
N
MODBUS SLAVE ID
1 … 248
248
1 to 247
1