D. enter access level 2, H. set the relay passwords with the pas command, Apply current and voltage signals to the relay – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual
Page 185

Rockwell Automation Publication 825-UM004D-EN-P - November 2012
185
Firmware Upgrade Instructions Chapter 13
d. Enter Access Level 2.
e. Issue
STATUS command, and verify that the relay status is OK.
f. Set the relay clock and calendar using the
DATE and TIME commands.
g. Set the Relay and Port settings using the following commands:
SET,
SET M, and SET P.
h. Set the relay passwords with the
PAS command.
10.
Set the communications software settings (baud rate, number of data bits,
number of stop bits) to agree with the port settings of the 825-P.
11.
Issue the
STATUS command, and then verify that all relay self-test results
are OK.
12.
Apply current and voltage signals to the relay.
13.
Issue the
METER command, and then verify that the current and voltage
signals are correct.
The relay is now ready for your commissioning procedure.