A- specifications, Electrical ratings, Main circuits – Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual
Page 187: 400 v ac, 240v ac, 5 kv, 50/60 hz ± 3 hz, 67…300v ac (line-to-line), 80…1.1 ue, 300v ac

Rockwell Automation Publication 825-UM004D-EN-P - November 2012
187
Appendix
A
Specifications
Electrical Ratings
Main Circuits
825 Converter Module
MCM2
MCM5
MCM20
MCM180
MCM420
MCM630N
825-MCM Converter Modules
Rated Operating Voltage U
e
—
400 V AC
240V AC
690V AC
600V AC
1,000V AC
600V AC
IEC:
CSA/UL:
Rated Impulse Strength U
imp
2.5 kV
6 kV
8 kV
Operating Current Range (A)
0.5-2.5
1-5
2.5-20
20-180
160-420
160-630
Rated Continuous Thermal Current
(A)
3
6
24
216
504
756
Rated Saturation Current
30
60
240
1350
3400
4600
Rated Frequency
50/60 Hz ± 3 Hz
Voltage Input Option Card
Rated Operating Voltage U
e
67…300V AC (line-to-line)
Operating Range
0.80…1.1 U
e
Rated Continuous Voltage
300V AC
Rated Insulation Voltage U
i
300V AC
Rated Impulse Strength U
imp
4 kV
Rated Frequency
50/60 Hz ± 5 Hz
Transition Voltage
5…15V
20…79V
PTC Thermistor Input
Type of Control Unit
Mark A
Max. No. of Sensors in Series
6
Max. Cold Resistance of PTC Sensor
Chain
1500
Ω
Trip Resistance
3400
Ω
± 150
Ω
Reset Resistance
1500
Ω
…1650
Ω
Short Circuit Trip Resistance
25
Ω
±
10
Ω