Rockwell Automation 825-P Modular Protection System for Motors User Manual User Manual
Page 230

230
Rockwell Automation Publication 825-UM004D-EN-P - April 2012
Chapter B Parameter List
Historical
Data
419
40320
NO. EVENT LOGS
0
5
—
1
—
Get
420
40321
400321
EVENT LOG SEL.
0
5
—
1
—
Get/Set
421
40322
EVENT TIME ss
0
5999
—
1
—
Get
422
40323
EVENT TIME mm
0
59
—
100
—
Get
423
40324
EVENT TIME hh
0
23
—
1
—
Get
424
40325
EVENT DAY dd
1
31
—
1
—
Get
425
40326
EVENT DAY mm
1
12
—
1
—
Get
426
40327
EVENT DAY yy
2000
9999
—
1
—
Get
427
40328
EVENT TYPE
0=No Trip
—
—
—
Get
1=Overload Trip
2=Lockd Rotor Trip
3=Undercurr Trip
4=Jam Trip
5=Curr Imbal Trip
6=Short Ckt Trip
7=Ground Flt Trip
8=Speed Sw Trip
9=Undervolt Trip
10=Overvolt Trip
11=Underpower Trip
12=Pwr Factor Trip
13=React Pwr Trip
14=Phase Rev Trip
15=Underfreq Trip
16=Overfreq Trip
17=RTD Trip
18=PTC Trip
19=Start Time Trip
20=MCM/CWE Fail
21=RTD Fail Trip
22=PTC Fail Trip
23=Reserved
24=Trigger
25=CommIdleLossTrip
26=Remote Trip
27=Comm Fail Trip
28=TestButton Trip
428
40329
EVENT L1
0
65535
—
1
A
Get
Group
DeviceNet
Param No.
Modbus Register
Parameter Name
Min
Max
Default
Scale
Factor
Units
Access
Read (0x03h)
Write (0x06h)