Chapter 10 Modbus RTU Communications
62h Read Enumeration
Text Command
The 825-P uses this function to allow a Modbus master to read parameter
enumeration or bit enumeration values (setting lists) from the relay. One
parameter enumeration is read in each query.
Table 80 - 62h Read Enumeration Text Command
The relay responses to errors in the query are shown below:
Table 81 - 61h Read Parameter Enumeration Text Query Error Messages
Bytes
Field
Requests from the master must have the following format:
1 byte
Slave Address
1 byte
Function Code (62h)
2 bytes
Parameter Number
1 byte
Enumeration Index
2 bytes
CRC-16
A successful response from the slave will have the following format:
1 byte
Slave Address
1 byte
Function Code (62h)
2 bytes
Parameter Number
1 byte
Enumeration Index
16 bytes
Enumeration Text
2 bytes
CRC-16
Error
Error Code Returned
Communication
Counter Increments
Illegal parameter to read
Illegal Data Value (03h)
Illegal Register