Publication 193-UM010A-EN-P – January 2008

3-4 PROFIBUS Configuration

Resetting to the Factory Default Values

Parameter 25, Set to Defaults, allows the installer to reset all parameter settings (including trip
logs) to the factory default values.

Parameter Group Listing

The 193-EPRB PROFIBUS Module contains six parameter groups:

Monitor Group

IMPORTANT

Resetting to factory default values also resets the node address of the
PROFIBUS module to its default value of 126.

Table 3.3 Parameter Groups

Monitor parameters

Advanced Setup

Reset/Lock

I/O Setup

Trip History

PROFIBUS Setup

1 Average %FLA

8 Trip Enable

19 Trip Reset

22 OutA Pr FltState

30 Trip Log 0

35 SSA Node Address

2%Therm Utilized

9 Warning Enable

20 Program Lock

23 OutA Pr FltValue

31 Trip Log 1

3 Trip Status

10 Single/Three Ph

21 Set to Defaults

24 OutA Pb FltState

32 Trip Log 2

4 Warning Status

11 OL Reset Mode

25 OutA Pb FltValue

33 Trip Log 3

5 Device Status

12 OL Warning Level

26 OutA Pb IdlState

34 Trip Log 4

6 Firmware Revision

13 Jam Inhibit Time

27 OutA Pb IdlValue

7 Serial Number

14 Jam Trip Delay

28 IN1 Assignment

15 Jam Trip Level

29 IN2 Assignment

16 Jam Warn Level

17 UL Inhibit Time

18 UL Warn Level

Average %FLA

Index No.

1

This parameter reports the average motor current. The value is
reported as a percentage of motor rated current (dial setting on
the E1 Plus Overload Relay), and is reported in increments of 5.

Access Rule

Read

Size

2 bytes

Group

Monitor

Units

%FLA

Min. Value

0

Max. Value

1275

Default Value

None

% Therm Utilized

Index No.

2

This parameter reports the percent thermal utilization of the
connected motor.

Access Rule

Read

Size

1 byte

Group

Monitor

Units

%

Min. Value

0

Max. Value

100

Default Value

None