Trip history group – Rockwell Automation 193-EPRB Profibus Side Mount Module for the E1 Plus Overload Relay User Manual User Manual

Page 25

Advertising
background image

Publication 193-UM010A-EN-P – January 2008

PROFIBUS Configuration 3-11

Trip History Group

OutA Pb IdlValue

Index No.

27

This parameter determines the state that Output A assumes
when the network is idle and parameter 26 is set to “0”.

Access Rule

Read/Write

Size

1 byte

Group

I/O Setup

Units

Min. Value

0 = Open

Max. Value

1 = Closed

Default Value

0

IN1 Assignment

Index No.

28

This parameter allows the user to assign a specific function
to the discrete IN1 input.

Access Rule

Read/Write

Size

1 byte

Group

I/O Setup

Units

Min. Value

Max. Value

0 = Normal
1 = Trip reset
2 = OL Contact

Default Value

0

IN2 Assignment

Index No.

29

This parameter allows the user to assign a specific function
to the discrete IN2 inputs.

Access Rule

Read/Write

Size

1 byte

Group

I/O Setup

Units

Min. Value

Max Value

0 = Normal
1 = Trip Reset
2 = OL Contact

Default Value

0

Trip Log 0

Index No.

30

This parameter records the latest trip.

Access Rule

Read

Size

2 byte

Group

Trip History

Units

Min. Value

See Trip Status table

Max. Value

See Trip Status table

Default Value

None

Trip Log 1

Index No.

31

This parameter records the trip previous to Trip Log 0.

Access Rule

Read

Size

2 bytes

Group

Trip History

Units

Min. Value

See Trip Status table

Max. Value

See Trip Status table

Default Value

None