3-10 PROFIBUS Configuration

I/O Setup Group

OutA Pr FltState

Index No.

22

This parameter, in conjunction with parameter 23,
defines how Output A will respond when a trip occurs.
When set to “1”, Output A will continue to operate as
commanded via the network. When set to “0”, Output A
will open or close as determined by the setting of
parameter 23.

Access Rule

Read/Write

Size

1 byte

Group

I/O Setup

Units

Min. Value

0 = Go To FltValue (#23)

Max. Value

1 = Ignore Fault

Default Value

0

OutA Pr FltValue

Index No.

23

This parameter determines the state that Output A assumes
when a trip occurs and Parameter 22 is set to “0”.

Access Rule

Read/Write

Size

1 byte

Group

I/O Setup

Units

Min. Value

0 = Open

Max. Value

1 = closed

Default Value

0

OutA Pb FltState

Index No.

24

This parameter, in conjunction with Parameter 25,
defines how Output A will respond when a PROFIBUS
network fault occurs. When set to “1”, Output A will
hold the state prior to PROFIBUS fault occurrence. When
set to “0”, Output A will open or close as determined by
the setting of Parameter 25.

Access Rule

Read/Write

Size

1 byte

Group

I/O Setup

Units

Min. Value

0 = Go To FltValue (#25)

Max. Value

1 = Hold Last State

Default Value

0

OutA Pb FltValue

Index No.

25

This parameter determines the state that Output A assumes
when a PROFIBUS network fault occurs and Parameter 24 is
set to “0”.

Access Rule

Read/Write

Size

1 byte

Group

I/O Setup

Units

Min. Value

0 = Open

Max. Value

1 = Closed

Default Value

0

OutA Pb IdlState

Index No.

26

This parameter, in conjunction with parameter 27,
defines how Output A will respond when the PROFIBUS
network is idle. When set to “1”, Output A will hold the
state prior to PROFIBUS fault occurrence. When set to
“0”, Output A will open or close as determined by the
setting in Parameter 27. The Pb Flt parameters
supersede the Pb Idl parameters.

Access Rule

Read/Write

Size

1 byte

Group

I/O Setup

Units

Min. Value

0 = Go To IdlValue (#27)

Max. Value

1 = Hold Last State

Default Value

0