3-8 PROFIBUS Configuration
Jam Inhibit Time
Index No.
13
This parameter defines the amount of time for which jam
detection is inhibited during a motor starting sequence.
Access Rule
Read/Write
Size
1 byte
Group
Advanced Setup
Units
Seconds
Min. Value
0
Max. Value
250
Default Value
10
Jam Trip Delay
Index No.
14
This parameter allows the installer to program a time
duration for which a jam condition must exist at the
programmed level prior to the device tripping.
Access Rule
Read/Write
Size
1 byte
Group
Advanced Setup
Units
Seconds
Min. Value
0.5
Max. Value
25.0
Default Value
5.0
Jam Trip Level Index
No.
15
This parameter sets the jam trip level.
Access Rule
Read/Write
Size
2 bytes
Group
Advanced Setup
Units
% FLA
Min. Value
150
Max. Value
600
Default Value
250
Jam Warn Level
Index No.
16
This parameter sets the jam warning level.
Access Rule
Read/Write
Size
2 bytes
Group
Advanced Setup
Units
% FLA
Min. Value
100
Max. Value
600
Default Value
150
UL Inhibit Time
Index No.
17
This parameter defines the amount of time for which
underload detection is inhibited during a motor starting
sequence.
Access Rule
Read/Write
Size
1 byte
Group
Advanced Setup
Units
Seconds
Min. Value
0
Max. Value
250
Default Value
10