Publication 193-UM010A-EN-P – January 2008

3-8 PROFIBUS Configuration

Jam Inhibit Time

Index No.

13

This parameter defines the amount of time for which jam
detection is inhibited during a motor starting sequence.

Access Rule

Read/Write

Size

1 byte

Group

Advanced Setup

Units

Seconds

Min. Value

0

Max. Value

250

Default Value

10

Jam Trip Delay

Index No.

14

This parameter allows the installer to program a time
duration for which a jam condition must exist at the
programmed level prior to the device tripping.

Access Rule

Read/Write

Size

1 byte

Group

Advanced Setup

Units

Seconds

Min. Value

0.5

Max. Value

25.0

Default Value

5.0

Jam Trip Level Index

No.

15

This parameter sets the jam trip level.

Access Rule

Read/Write

Size

2 bytes

Group

Advanced Setup

Units

% FLA

Min. Value

150

Max. Value

600

Default Value

250

Jam Warn Level

Index No.

16

This parameter sets the jam warning level.

Access Rule

Read/Write

Size

2 bytes

Group

Advanced Setup

Units

% FLA

Min. Value

100

Max. Value

600

Default Value

150

UL Inhibit Time

Index No.

17

This parameter defines the amount of time for which
underload detection is inhibited during a motor starting
sequence.

Access Rule

Read/Write

Size

1 byte

Group

Advanced Setup

Units

Seconds

Min. Value

0

Max. Value

250

Default Value

10