Specifications, Appendix – Rockwell Automation 193-EPRB Profibus Side Mount Module for the E1 Plus Overload Relay User Manual User Manual

Page 31

Advertising
background image

1

Publication 193-UM010A-EN-P – January 2008

Appendix

A

Specifications

Terminal Ratings:

Terminal Screw

M3

Wire Cross Section

See wiring diagram section

Torque

0.5…0.6 N•m (4.4…5.3 lb.-in)

Degree of Protection

IP20

Power Supply Ratings:

Rated Supply Voltage Us

24V DC

Rated Operating Range Ue

20.4 - 26.4

Rated Supply Current Ie

0.1 A

Maximum Surge Current at Power-Up

2.5 A

Maximum Power Consumption

2.5 W

Maximum Power Interruption Time

0.5ms

Output Relay Ratings:

Terminals
OUT A:

13/14

Type of Contacts

Form A
SPST - NO

Rated Thermal Current I

the

5 A

Rated Insulation Voltage Ui

300V AC

Rated Operating Voltage Ue

240V AC

Rated Operating Current Ie

3 A (at 120V AC), 1.5 A (at 240V AC)
0.25 A (at 110V DC), 0.1 A (at 220V DC)

Minimum Operating Current

10 mA at 5V DC

Rating Designation

B300

Utilization Category

AC-15

Resistive Load Rating
(p.f.=1.0)

5 A, 250V

AC

5 A, 30V DC

Inductive Load Rating
(p.f.=0.4), (L/R=7 ms)

2 A, 250V AC
2 A, 30V DC

Short Circuit Current Rating

1,000 A

Recommended Control Circuit Fuse

KTK-R-6
(6 A, 600V)

Rated Number of Operations
Out A:
W/100-C-09…100-C43
W/100-C-60…100-C85
W/NEMA Size 0…2
W/NEMA Size 3

5,000,000
2,500,000
1,000,000
300,000

Input Ratings:

Terminals
IN 1:
IN 2:
SSV (Sensor Supply Voltage)

1
2
3

Supply Voltage (provided by module)

20.4 - 26.4V DC

Advertising