Appendix

B

PROFIBUS Information

Structure of the "Set Prm
Data"-telegram

During startup of the network, it is possible to force start-up values for all writable parameters
through the User Prm Data. The module will use the settings provided that the "Parameter
Initialization"-setting (User Prm Data byte #3) is set as "Enabled". Note that this will result in
any previous settings to be replaced by the settings from the User Prm Data.

Electronic Data Sheet

Electronic data sheet (GSD) files are specially formatted ASCII files that provide all of the
information necessary for a PROFIBUS configuration tool to access and alter the parameters of
a device. The GSD file contains all the parameter information of a device: number of
parameters, groupings, parameter name, min, max, and default values, units, data format and

Table B.5 Structure of the "Set Prm Data"-telegram

Byte no.

Name

Description

0-2

DP-V1 standard bytes

-

3

Parameter Initialization

Enables/Disables initialization of parameters via parameterization data.
1= Enabled
0= Disabled

4-5

Trip Enable

Initial value for parameter 8, Trip Enable

6-7

Warning Enable

Initial value for parameter 9, Warning Enable

8

Single/Three Ph

Initial value for parameter 10, Single/Three Ph

9

OL Reset mode

Initial value for parameter 11, OL Reset mode

10

OL Warning Level (%Therm. Util.)

Initial value for parameter 12, OL Warning Level

11

Jam Inhibit Time (1s)

Initial value for parameter 13, Jam Inhibit Time

12

Jam Trip Delay (0.1s)

Initial value for parameter 14, Jam Trip Delay

13-14

Jam Trip Level (%FLA)

Initial value for parameter 15, Jam Trip Level

15-16

Jam Warn Level (%FLA)

Initial value for parameter 16, Jam Warn Level

17

UL Inhibit Time (1s)

Initial value for parameter 17, UL Inhibit Time

18

UL Warn Level (%FLA)

Initial value for parameter 18, UL Warn Level

19

Program Lock

Initial value for parameter 20, Program Lock

20

OutA Pr State/Value

Bit 0: Initial value for parameter 22, OutA Pr FltState
Bit 1: Initial value for parameter 23, OutA Pr FltValue
(Other bits: Not used, Must be set to 0)

21

OutA Pb State/Value

Bit 0: Initial value for parameter 24, OutA Pb FltState

Bit 1: Initial value for parameter 25, OutA Pb FltValue

(Other bits: Not used, Must be set to 0)

22

OutA Pb IdlState/Value

Bit 0: Initial value for parameter 26, OutA Pb IdlState

Bit 1: Initial value for parameter 27, OutA Pb IdlValue

(Other bits: Not used, Must be set to 0)

23

IN1 Assignment

Initial value for parameter 28, IN1 Assignment

24

IN2 Assignment

Initial value for parameter 29, IN2 Assignment