Rockwell Automation 193-EPRB Profibus Side Mount Module for the E1 Plus Overload Relay User Manual User Manual

Page 21

Advertising
background image

Publication 193-UM010A-EN-P – January 2008

PROFIBUS Configuration 3-7

Warning Enable

Index No.

9

This parameter allows the installer to enable or
disable the warning functions separately. All
warning functions are disabled from the
factory.
1 = Enabled
0 = Disabled

Access Rule

Read/Write

Size

2 bytes

Group

Advanced Setup

Units

Min. Value

0000000000000000

Max. Value

0000000001101101

Default Value

0000000000000000

Bit

Function:

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

X

Overload

X

Not Used

X

Jam

X

Underload

X

Not Used

X

Comm Fault

X

Comm Idle

X

X

X

X

X

X

X

X

X

Not Used

Single/Three Ph

Index No.

10

This parameter configures the PROFIBUS Module for single-
or three-phase application. This parameter should be set to
“Single Phase" when Bulletin 193S or 592S devices are
employed.

Access Rule

Read/Write

Size

1 byte

Group

Advanced Setup

Units

Min. Value

0 = Single-Phase

Max. Value

1 = Three-Phase

Default Value

1

OL Reset Mode

Index No.

11

This parameter defines whether a trip can be automatically
or manually reset. This setting overrides the E1 Plus DIP
switch adjustment while the PROFIBUS Module is powered.
Note, however, that the E1 Plus manual reset button,
accessible at the front, is always active.

Access Rule

Read/Write

Size

1 byte

Group

Advanced Setup

Units

Min. Value

0 = Manual

Max. Value

1 = Automatic

Default Value

0

OL Warning Level

Index No.

12

This parameter sets the overload warning level.

Access Rule

Read/Write

Size

1 byte

Group

Advanced Setup

Units

% Thermal Utilization

Min. Value

0

Max. Value

100

Default Value

90