Reset/lock group – Rockwell Automation 193-EPRB Profibus Side Mount Module for the E1 Plus Overload Relay User Manual User Manual
Page 23
Publication 193-UM010A-EN-P – January 2008
PROFIBUS Configuration 3-9
Reset/Lock Group
UL Warn Level
Index No.
18
This parameter sets the underload warning level.
Access Rule
Read/Write
Size
1 byte
Group
Advanced Setup
Units
% FLA
Min. Value
30
Max. Value
100
Default Value
70
Trip Reset
Index No.
19
This parameter provides the user with the capability of
resetting a trip over the PROFIBUS network. After a trip is
reset, the parameter automatically returns to a “Ready”
state.
Access Rule
Read/Write
Size
1 byte
Group
Reset/Lock
Units
—
Min. Value
0 = Ready
Max. Value
1 = Reset Trip
Default Value
0
Program Lock
Index No.
20
This parameter prohibits the device parameters from being
altered when set to “Locked”. It must be set to “Unlocked”
to allow parameter modification.
Access Rule
Read/Set
Size
1 byte
Group
Reset/Lock
Units
—
Min. Value
0 = Unlocked
Max. Value
1 = Locked
Default Value
0
Set To Defaults
Index No.
21
This parameter allows the user to reset the parameter
settings to the factory default values. After parameter
values have been reset to the factory default settings, the
parameter automatically returns to a “Ready” state.
Access Rule
Read/Write
Size
1 byte
Group
Reset/Lock
Units
—
Min. Value
0 = Ready
Max. Value
1 = Reset Defaults
Default Value
0