Publication 193-UM010A-EN-P – January 2008

PROFIBUS Configuration 3-9

Reset/Lock Group

UL Warn Level

Index No.

18

This parameter sets the underload warning level.

Access Rule

Read/Write

Size

1 byte

Group

Advanced Setup

Units

% FLA

Min. Value

30

Max. Value

100

Default Value

70

Trip Reset

Index No.

19

This parameter provides the user with the capability of
resetting a trip over the PROFIBUS network. After a trip is
reset, the parameter automatically returns to a “Ready”
state.

Access Rule

Read/Write

Size

1 byte

Group

Reset/Lock

Units

Min. Value

0 = Ready

Max. Value

1 = Reset Trip

Default Value

0

Program Lock

Index No.

20

This parameter prohibits the device parameters from being
altered when set to “Locked”. It must be set to “Unlocked”
to allow parameter modification.

Access Rule

Read/Set

Size

1 byte

Group

Reset/Lock

Units

Min. Value

0 = Unlocked

Max. Value

1 = Locked

Default Value

0

Set To Defaults

Index No.

21

This parameter allows the user to reset the parameter
settings to the factory default values. After parameter
values have been reset to the factory default settings, the
parameter automatically returns to a “Ready” state.

Access Rule

Read/Write

Size

1 byte

Group

Reset/Lock

Units

Min. Value

0 = Ready

Max. Value

1 = Reset Defaults

Default Value

0