Fault definitions – Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 146

Advertising
background image

Diagnostics

9-3

Fault Definitions

Power Loss

Power loss indicates that an input power phase is not present. The
controller’s LCD display will identify the missing phase.

Note: If all three phases are absent when a start command is issued,

the LCD will display “Starting” without motor rotation.

Line Fault

①

Line fault with the affected phase displayed identifies three possible
pre-start conditions.

•

Phase loss

•

Load loss

•

Shorted SCR

Line fault with no phase indication is displayed when one of the
following conditions occurs while the SMC Dialog Plus controller is
in the run mode.

•

Phase loss

•

Load loss

•

Shorted SCR

Phase Reversal

Phase reversal is indicated when the incoming power to the SMC
Dialog Plus controller is in any sequence other than ABC. This pre-
start protective feature can be disabled.

Overvoltage and Undervoltage Protection

①

Overvoltage and undervoltage protection are user-defined as a
percentage of the programmed line voltage. The SMC Dialog Plus
controller continuously monitors the three supply phases. The
calculated average is then compared to the programmed trip level.

①

Phase loss, overvoltage, and undervoltage protection are disabled during braking operation.