Specifications
①
Assumes the Bulletin 825 converter module is utilized.
②
The SMC Dialog Plus controller calculates the current values to two decimal place resolution while
displaying only to tenths of Amps. The display accuracy provided is, therefore, reduced by the
truncation. The affect of truncation on accuracy will be dependent on the magnitude of the value.
③
Assumes a balanced supply.
Other Ratings
UL/CSA/NEMA
IEC
EMC Emission Levels
Conducted Radio Frequency
Emissions
Class A
Radiated Emissions
Class A
EMC Immunity Levels
Electrostatic Discharge
8kV Air Discharge
Radio Frequency Electromagnetic
Field
Per IEC 947-4-2
Fast Transient
Per IEC 947-4-2
Surge Transient
Per IEC 947-4-2
Overload Characteristics:
Type
Solid-state thermal overload with phase loss
Current Range
1.0–999.9 Amps
Trip Classes
10, 15, 20, and 30
Trip Current Rating
120% of Motor FLC
Number of Poles
3
Metering Accuracy
Voltage
± 2%
Current
± 5%
① ②
kW
± 10%
kWH
± 10%
Displacement Power Factor
± 3%
③
Converter Module Output
Cat. No.:
825-MCM20
825-MCM180
825-MCM630
78.8 mV/A
9.85 mV/A
1.231 mV/A