Parameter information, Appendix – Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual
Page 170

Appendix
B
Parameter Information
Table B.1
Parameter List
①
Read-only capability.
Group
Parameter
Description
Parameter
Number
Display
Units
Scale
Factor
Minimum
Maximum
Default
Setting
User
Setting
Metering
①
Voltage
Phase A–B
1
Volts
1
—
—
—
—
Voltage
Phase B–C
2
Volts
1
—
—
—
—
Voltage
Phase C–A
3
Volts
1
—
—
—
—
Current
Phase A
4
Amps
10
—
—
—
—
Current
Phase B
5
Amps
10
—
—
—
—
Current
Phase C
6
Amps
10
—
—
—
—
Wattmeter
7
kW
10
—
—
—
—
Kilowatt
Hours
8
kWH
1
—
—
—
—
Elapsed
Time
9
Hours
1
—
—
—
—
Power
Factor
10
—
100
—
—
—
—
Motor Thermal
Usage
11
%
1
—
—
—
—
Faults
Clear Fault
18
—
—
No, Yes
No
—
Fault
Buffer #1
①
19
—
1
—
—
—
—
Fault
Buffer #2
①
20
—
1
—
—
—
—
Fault
Buffer #3
①
21
—
1
—
—
—
—
Fault
Buffer #4
①
22
—
1
—
—
—
—
Fault
Buffer #5
①
23
—
1
—
—
—
—
Basic Setup
SMC Option
①
14
—
—
Standard, Soft Stop, Pump Control, Preset Slow
Speed, Smart Motor Braking, Accu-Stop, or Slow
Speed with Braking
—
Starting Mode
28
—
—
Soft Stop, Current Limit
Soft Start
Ramp Time #1
30
Seconds
1
0
30
10
Initial Torque
#1
31
% LRT
1
0
90
70
Current Limit
Level
34
% FLC
1
50
600
50
Kickstart Time
35
Seconds
10
0.0
2.0
0.0 (Off)