Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual
Page 171

B-2
Parameter Information
Table B.1 (cont.) Parameter List
Group
Parameter
Description
Parameter
Number
Display
Units
Scale
Factor
Minimum
Maximum
Default
Setting
User
Setting
Basic Setup
(cont.)
Stall Delay
37
Seconds
10
0.0
10.0
0 (Off)
Energy Saver
38
—
—
Off, On
Off
Aux. Contacts
1 and 2
39
—
—
Normal, Up-to-speed
Normal
Aux. Contact
3
40
—
—
Normal, Fault
Normal
Contact 3
Config
41
—
—
N.O., N.C.
N.O.
Parameter
Mgmt.
17
—
—
Ready, Default Init.
Recll Frm EE,Store In EE
Ready
Control Options
Soft Stop
Soft Stop
Time
42
Seconds
1
0
60
0
Pump Control
Starting
Mode
28
—
—
Soft Start, Current Limit,
and Pump Start
Soft Start
Pump Stop
Time
42
Seconds
1
0
120
Preset Slow Speed
Slow Speed
Select
44
—
—
Low, High
High
Slow Speed
Direction
45
—
—
Reverse, Forward
Forward
Slow Accel
Current
46
% FLC
1
0
450
0
Slow Running
Current
47
% FLC
1
0
450
0
SMB Smart Motor Braking
Braking
Current
48
% FLC
1
0
400
0
Accu-Stop
Slow Speed
Select
44
—
—
Low, High
High
Slow Accel
Current
46
% FLC
1
0
450
0
Slow Running
Current
47
% FLC
1
0
450
0
Braking
Current
48
% FLC
1
0
400
0
Stopping
Current
51
% FLC
1
0
400
0