Standard controller wiring diagrams (cont.) – Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 62

Advertising
background image

3-16

Wiring

Standard Controller
Wiring Diagrams (cont.)

Figure 3.20 Typical Wiring Diagram for Single Speed Reversing Applications

①

Customer supplied.

②

Refer to the controller nameplate to verify the rating of the control power input rating.

Notes:

(1)

Minimum transition time for reversing direction is 1/2 second.

(2)

Phase Reversal protection must be disabled in reversing applications.

Stop

➀

OFF

➀

FOR

REV

F

F

F

R

R

R

➁

3-Phase

Input Power

Branch

Protection

➀

Reversing

Contactors

➀

Fast-acting

SCR Fuses

(optional)

➀

Bulletin 825

Coverter

Module

(optional)

➀

M

➀

➀

➀

➀

F

R

L1/1

L2/3

L3/5

T1/2

T2/4

T3/6

➀

➀

➀

➀

➀

➀

11 12 13 14 15 16 17 18 19 20

21 22 23 24 25 26 27 28 29 30

Internal

Auxiliary
Contacts

SMC Dialog Plus

Controller

SMC Dialog Plus

Control Terminals