Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 173

Advertising
background image

B-4

Parameter Information

Table B.1 (cont.) Parameter List

①

Read-only capability.

②

The scale factor is 100 when Motor FLC, parameter 70, has a programmed value of up to 10.0 Amps; above 10.0 Amps, the scale factor is 10.

Group

Parameter

Description

Parameter

Number

Display

Units

Scale

Factor

Minimum

Maximum

Default
Setting

User

Setting

Calibrate

Overload

Class

36

—

—

Off, 10, 15, 20, and 30

Off

Overload

Reset

88

—

—

Manual-Auto

Manual

Motor HP

Rating

79

HP

10

0.0

6,553.5

0.0

Motor kW

Rating

80

kW

10

0.0

6,553.5

0.0

Line Voltage

69

Volts

1

0

9999

480

Motor FLC

70

Amps

10

1.0

999.9

1.0

Service

Factor

84

—

100

0.01

1.99

1.15

Motor Code

Letter

72

—

—

A, B, C, D, E, F, G, H, J, K, L,

M, N, P, R, S, T, U, and V

G

LRC Ratio

81

—

10

0.0

19.9

0.0

Converter

Rating

74

—

—

None, 20, 180, 630

None

CT Ratio

75

—

—

5, 50, 75, 100, 150, 200,

250, 300, 400, 500, 600, 750,

800, 1000, 1200 :5

5:5

Calibration

76

—

—

Off, Activate

Off

Enter Calib.

Amps

77

Amps

②

0.01

999.9

0.0

Current

Phase A

①

4

Amps

10

—

—

—

Parameter

Mgmt.

17

—

—

Ready, Default Init.

Recll Frm EE,Store In EE

Ready

Advertising