Using Unscheduled Messaging

Publication 1336 FORCE–5.18 ––March, 1999

The Maximum Trend Size Available function allows you to
determine the size of the trend buffer. This function always returns
500.

PLC Block Transfer Instruction Data

PLC Message Write instruction length:

3 words

PLC Message Read instruction length:

3 words

Header

Word 1

Header

Word 1

Header

Word 2

Header

Word 2

Header

Word 3

Maximum Trend Size

Message Structure

Header

Word 3

0

PLC Decimal Value

4097

PLC Decimal Value

4097 –– Message OK

–28671 –– Message Error

Message Length

3

Message Length

3

PLC Request –– PLC Message Write

Drive Response –– PLC Message Read

Message Operation

You can use the Maximum Trend Size Available function to
determine the size of the trend buffer. This function always returns
500.

Example

In this example, a Maximum Trend Size Available request was sent
to the drive. The drive returned a value of 500 in word 3.

1

0

N7:10

2

3

4

5

6

7

8

9

N7:90

PLC MSG
Write File

PLC MSG
Read File

Data Format

0

500

3

3

4097

4097

Trend File

Maximum Trend Size Available