Fault queue, Plc block transfer instruction data, Message operation – Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual

Page 67: Example, Trip fault queue number

Advertising
background image

4–25

Using Unscheduled Messaging

Publication 1336 FORCE–5.18 ––March, 1999

The Trip Fault Queue Number message provides the fault queue
number of the fault that caused the drive to trip.

PLC Block Transfer Instruction Data

PLC MSG Write instruction length:

3 words

PLC MSG Read instruction length:

4 words

Message

3

Header

Word 1

Header

Word 1

PLC Decimal Value

1793

Header

Word 2

Header

Word 3

0

PLC Decimal Value

1793 –– Message OK

Header

Word 2

Header

Word 3

0

-30975 –– Message Error

Header

Word 4

Fault Queue Size

Message Structure

0

PLC Request –– PLC Message Write

Drive Response –– PLC Message Read

Message Operation

The Trip Fault Queue Number function provides the entry number of
the fault in the fault queue that tripped the drive The PMR response
contains that number in word 4. The Fault Queue Number is 0 when
the drive is not faulted.

If an error has occurred in the block transfer, word 2 of the response
will be -30975.

Example

In this example, the first entry in the drive fault queue has caused the
drive to trip. Word 4 of the PMR indicates the entry number.

1

0

N7:10

2

3

4

5

6

7

8

9

N7:90

PLC MSG
Write File

PLC MSG
Read File

Data Format

0

0

1

3

0

1794

1794

These values vary depending on parameters and products.

Fault Queue

Trip Fault Queue Number