Link read, Plc block transfer instruction data, Message operation – Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual

Page 76: Example, Link parameter read

Advertising
background image

4–34

Using Unscheduled Messaging

Publication 1336 FORCE–5.18 ––March, 1999

The Link Parameter Read message reads the source parameter
number that is linked to the specified sink parameter.

PLC Block Transfer Instruction Data

PLC Message Write instruction length:

3 words

PLC Message Read instruction length:

4 words

Message Length

3

Header

Word 1

Header

Word 1

PLC Decimal Value

2304

Header

Word 2

Header

Word 3

Header

Word 2

Header

Word 3

PLC Decimal Value

2304 –– Message OK

Sink Parameter Link

-30464 –– Message Error

0

Parameter Number

Data

Word 4

Message Structure

Source Parameter

Number

PLC Request –– PLC Message Write

Drive Response –– PLC Message Read

Message Operation

The Link Parameter Read function specified in the PMW reads the
source parameter that is linked to the requested sink parameter,
defined in word 3 of the header message. The source parameter is
returned in word 4 of the PMR.

If an error has occurred, word 2 of the PMR returns a value of
-30464.

Example

In this example, the link associated with parameter 101 was
requested from the drive. The PMW header message word 4 defines
the sink parameter of the requested link with a value of 101. The
linked source parameter 330 is returned in word 4 of the PMR.

1

0

N7:0

2

3

4

5

6

7

8

9

N7:90

PLC MSG
Write File

PLC MSG
Read File

Data Format

101

0

101

330

3

0

2304

2304

Link Read

Link Parameter Read