Using Unscheduled Messaging

Publication 1336 FORCE–5.18 ––March, 1999

The Scattered Parameter Link Read message returns a list of up to 30
links in the source-to-sink order found in the drive. The links do not
have to be in consecutive order.

PLC Block Transfer Instruction Data

PLC Message Write instruction length:

5-63 words

PLC Message Read instruction length:

5-63 words

Message Length

5-63

Header

Word 1

PLC Decimal Value

5

Header

Word 2

Data

Word 3

PLC Decimal Value

5 –– Message OK

-32763 –– Message Error

Data

Word 4

Number of Parameter

Links to Read

Parameter Number

1

Number of Parameter

Links to Read

Parameter

Number 1

Data

Word 6

Parameter Number

2

Data

Word 62

Parameter Number

30

Bit 15

Parameter

Number 2

Bit 15

Data

Word 63

Parameter

Number 30

Bit 15

Data

Word 7

Data

Word 5

Data

Word 63

Message Structure

0

0

0

Data

Word 7

Data

Word 6

Data

Word 5

Data

Word 4

Data

Word 3

Header

Word 2

Header

Word 1

0

Data

Word 62

Source Parameter

Number 1

Source Parameter

Number 2

Source Parameter

Number 30

PLC Request –– PLC Message Write

Drive Response –– PLC Message Read

Message Operation

The Scattered Parameter Link Read function requested in the PMW
reads up to 30 non-consecutive links made in the drive. You request
the desired link information by defining the sink parameters in the
PMW message.

Link Read