Trend file, Plc block transfer instruction data, All info – Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual
Page 112

4–70
Using Unscheduled Messaging
Publication 1336 FORCE–5.18 ––March, 1999
The All Info function allows you to read the set up information for a
trend file in a single message instead of reading the individual
parameters within the drive.
PLC Block Transfer Instruction Data
PLC Message Write instruction length:
3 words
PLC Message Read instruction length:
15 words
Header
Word 1
Header
Word 1
Header
Word 2
Header
Word 2
Header
Word 3
Trend Number
Message Structure
Header
Word 3
Trend Number
PLC Decimal Value
4098
PLC Decimal Value
4098 –– Message OK
–28670 –– Message Error
Message Length
3
Message Length
15
PLC Request –– PLC Message Write
Drive Response –– PLC Message Read
Data
Word 4
Trend Status
Data
Word 5
Trend Sample Size
Data
Word 6
Post Samples
Data
Word 7
Operator Data
Data
Word 8
Sample Time Rate
Data
Word 9
Mode
Data
Word 10
Comparison A Value
Data
Word 11
Comparison A Link
Data
Word 12
Comparison B Value
Data
Word 13
Comparison B Link
Data
Word 14
Sampling Input Parameter
Data
Word 15
Trend Output Parameter
Trend File
All Info