Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual
Page 175

6–33
Parameters
Publication 1336 FORCE–5.18 ––March, 1999
425
ICN Fault Select
[ICN Flt Sel]
ICN Flt Sel dictates whether the ControlNet Adapter
Board will report a fault condition if a PLC controller
communications fault occurs.
If bit is one, the condition is reported as a soft fault.
If a bit is zero, parameter 426 is checked to see
whether a warning condition should be reported.
Parameter Number
425
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
Bits
Factory Default
47 (2Fh)
Minimum Value
0
Maximum Value
127 (7Fh)
File – Group
Diagnostics – Fault Select/Status
Communication I/O – Fault Select/Status
When adapter is used:
Enums
Bits 7–4 Bit 3 Bit 2 Bit 1 Bit 0
Res/Pgm/Test (Flt 36023)
0 = No drive soft fault
1 = Drive soft fault
Last State
0 = Data zeroed
1 = Continue Operation
Using Last State
ICN Comm Loss (Flt 36021)
0 = No drive soft fault
1 = Drive soft fault
Class 1 Close
0 = No drive soft fault
1 = Drive soft fault
Bit 4: Class 3 Close
0 = No drive soft fault
1 = Drive soft fault
Bit 5: Class 1 Timeout
0 = No drive soft fault
1 = Drive soft fault
Bit 6: Class 3 Timeout
0 = No drive soft fault
1 = Drive soft fault
Bit 7: Reserved