Before you can transfer data between the ControlNet Adapter Board
and the analog I/O, you need to do the following:
1. Hard wire the analog I/O to the CNA Board terminals.
2. Set up the analog input and output configuration parameters in
the drive.
3. Create any user links, if appropriate.
Note: The ControlNet Adapter Board has been pre-configured for
your convenience. The pre-configured links are listed later in Figure
2.4.
Each terminal has parameters associated with it as shown here in the
analog I/O block diagram.
+10V REF
17
REF COM
18
–10V REF
19
OUT1
1
Par 401 Scale
COM1
2
Par 400 Offset
TB21
Analog Out #1
Analog Out 1
OUT2
3
Par 403 Scale
COM2
4
Par 402 Offset
Analog Out #2
Analog Out 2
OUT3
5
Par 405 Scale
COM3
6
Par 404 Offset
Analog Out #3
Analog Out 3
OUT4
7
Par 407 Scale
COM4
8
Par 406 Offset
Analog Out #4
Analog Out 4
339
IN1+
9
Par 393 Scale
IN1–
10
Par 392 Offset
Analog In #1
Analog In 1
340
IN2+
11
Par 395 Scale
IN2–
12
Par 394 Offset
Analog In #2
Analog In 2
341
IN3+
13
Par 397 Scale
IN3–
14
Par 396 Offset
Analog In #3
Analog In 3
342
IN4+
15
Par 399 Scale
IN4–
16
Par 398 Offset
Analog In #4
Analog In 4
Power
Supply
387
388
390
389
Setting Up the Analog I/O
"