Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual
Page 108

Programming
5-40
Faults Group
(continued)
[Cur Lim Trip En]
Parameter # 82
Factory Default ‘‘Default Run”
[Cur Lim Trip En]
Parameter Type Read & Write
This setting determines whether or not exceeding the
setting in [Current Limit] will cause a Diagnostic Current
Units Text
Setting ‘‘Trip @ I Lim”
A Diagnostic Current Limit Fault is generated
setting in [Current Limit] will cause a Diagnostic Current
Limit Fault (Fault F36).
‘‘Default Run”
No fault generated
[Line Loss Fault]
Parameter # 40
Factory Default ‘‘F03 Enable”
[Line Loss Fault]
Parameter Type Read & Write
This setting determines whether a 15% drop in DC Bus
voltage will have no effect on operation or cause a ‘‘Power
Loss Fault” (fault F03).
Units Text
Setting ‘‘UVolt Run”
‘‘Power Loss Fault” Disabled
Loss Fault (fault F03).
Important
:
The “Line Loss” alarm bit will be set when this
condition exists regardless of the parameter setting.
‘‘FO3 Enable”
Drive Trips at 85% of nominal bus voltage.