Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual
Page 83

Programming
5-15
This group contains parameters that are required to setup advanced functions of the drive such as custom
Volts per Hertz settings and dynamic braking.
Advanced
Setup
[Minimum Freq]
Parameter # 16
Factory Default 0 Hz
[Minimum Freq]
Parameter Type Read & Write
Minimum 0 Hz
This parameter sets the lowest frequency the drive will
output.
Important: All analog inputs to the drive (4-20mA, 0-10V,
Remote Pot) are scaled for the range [Minimum Freq] to
[Maximum Freq].
Units 1 Hz
Maximum 120 Hz
Important: This parameter can not be
programmed while the drive is running.
[Maximum Freq]
Parameter # 19
Factory Default 60 Hz
[Maximum Freq]
Parameter Type Read & Write
Minimum 40 Hz
This parameter sets the highest frequency the drive will
output.
Important: All analog inputs to the drive (4-20mA, 0-10V,
Remote Pot) are scaled for the range [Minimum Freq] to
[Maximum Freq]
Units 1 Hz
Maximum 400 Hz
Important: This parameter can not be
programmed while the drive is running.
[Base Frequency]
Parameter # 17
Factory Default 60 Hz
[Base Frequency]
Parameter Type Read & Write
Minimum 40 Hz
This value should be set to the motor nameplate Rated
Frequency.
Units 1 Hz
Maximum 400 Hz