Programming
5-10
Setup Group
(continued)
[Base Frequency]
Parameter # 17
Factory Default 60 Hz
[Base Frequency]
Parameter Type Read & Write
Minimum 40 Hz
This value should be set to the motor nameplate Rated
Frequency.
Units 1 Hz
Maximum 400 Hz
[Base Voltage]
Parameter # 18
Factory Default Max. Drive Rated Volts
[Base Voltage]
Parameter Type Read & Write
Minimum 25% of Max. Drive Rated Volts
This value should be set to the motor nameplate Rated
Voltage.
Units 1 Volt
Maximum 100% of Max. Drive Rated Volts
[Maximum Voltage]
Parameter # 20
Factory Default Max. Drive Rated Volts
[Maximum Voltage]
Parameter Type Read & Write
Minimum 25% of Max. Drive Rated Voltage
This parameter sets the highest voltage the drive will
output.
Units 1 Volt
Maximum 110% of Max. Drive Rated Volts
[Minimum Freq]
Parameter # 16
Factory Default 0 Hz
[Minimum Freq]
Parameter Type Read & Write
Minimum 0 Hz
This parameter sets the lowest frequency the drive will
output.
Important: All analog inputs to the drive (4-20mA, 0-10V,
Remote Pot) are scaled for the range [Minimum Freq] to
[Maximum Freq].
Units 1 Hz
Maximum 120 Hz
Important: This parameter can not be
programmed while the drive is running.