B-7
Table B.4 Parameter Grouping/User Settings
(continued)
Group Parameter Name
Parameter
Number
Display
Units
Drive Units
Scale Factor
➁
Minimum
Maximum
Factory Setting
User‘s
Setting
Minimum Freq
16
Hz
1
0
120
0
Maximum Freq
19
Hz
1
40
400
60
Base Frequency
17
Hz
1
40
400
60
Base Voltage
18
Volts
1
25% of DRV
100% of Max. Drive Rated Volts
Maximum DRV
Break Frequency
49
Hz
1
0
120
30
p
Break Voltage
50
Volts
1
0
50% of Max Drive Rated Volts
Drive Size
Dependent
t Up
Maximum Voltage
20
Volts
1
25% of DRV
110% of Max. Drive Rated Volts
Maximum DRV
Set
DC Boost Select
9
Text
➀
1
––
––
Break Point
anced
S
Start Boost
48
Volts
1
0
25% of Max. Drive Rated Volts
Drive Size
Dependent
d
va
n
Run Boost
83
Volts
1
0
25% of Max. Drive Rated Volt
0
Ad
v
PWM Frequency
45
kHz
10
2.0
8.0
4.0
Analog Invert
84
Text
➀
1
––
––
Disabled
4–20 mA Loss Sel
81
Text
➀
1
––
––
Stop/Fault
Stop Select
10
Text
➀
1
––
––
Ramp
DC Hold Time
12
Seconds
100
0.0
150.0
0.0
DC HoId Volts
13
Volts
1
0
25% of Max. Drive Rated Volts
0
DB Enable
11
Text
➀
1
––
––
Disabled
Motor Type
41
Text
➀
1
––
––
Induc/Reluc
Compensation
52
Text
➀
1
––
––
Comp
➀ Refer to Table B.1 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions.
➁ Refer to page B-2.