Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual
Page 96

Programming
5-28
Frequency Set Group
(continued)
[Skip Freq Band]
Parameter # 35
Factory Default 0 Hz
[Skip Freq Band]
Parameter Type Read & Write
Minimum 0 Hz
This parameter determines the band width around a [Skip
Frequency]. The band width is 2
[Skip Freq Band] –
1/2 the band above and 1/2 the band below the [Skip
Frequency] setting. “0” Disables All Skip Frequencies.
Units 1 Hz
Maximum 15 Hz
'
Figure 5.15 Skip Frequency Band
b
y
Two times
[Skip Freq Band]
Setting
'
Command Frequency
Skip Frequency
Frequency
Time
Drive Output
Frequency
Setting
a
[MOP Increment]
Parameter # 22
Factory Default 1.00 Hz/Sec
[MOP Increment]
Parameter Type Read & Write
Minimum 0.00 Hz/Sec
y
The MOP function is a digital solid-state circuit that
produces the same effect as rotating a speed reference
potentiometer with a small DC motor. This permits local
(HIM) or remote (TB2) control of the command
frequency. This parameter sets the rate of increase or
decrease to the [MOP Hertz] command frequency for
each input to the MOP Increment or MOP Decrement
terminals of TB2. (Requires the proper [Input Mode]
selection or serial communications.)
Units 1 Hz/Sec
Maximum 255 Hz/Sec
'
y
Hz
(Speed)
INC
Time
DEC