Table B.4 Parameter Grouping/User Settings
(continued)
Group Parameter Name
Parameter
Number
Display
Units
Drive Units
Scale Factor
➁
Minimum
Maximum
Factory Setting
User‘s
Setting
Input Mode
21
Text
➀
1
––
––
Three Wire
Freq Select 1
5
Text
➀
1
––
––
Adapter 1
Accel Time 1
7
Seconds
10
0.0
3600.0
10.0
Decel Time 1
8
Seconds
10
0.0
3600.0
10.0
Base Frequency
17
Hz
1
40
400
60
Base Voltage
18
Volts
1
25% of DRV
100% of Drive Rated Volts
Drive Rated Volts
p
Maximum Voltage
20
Volts
1
25% of DRV
110% of Drive Rated Volts
Drive Rated Volts
t Up
Minimum Freq
16
Hz
1
0
120
0
S
et
U
Maximum Freq
19
Hz
1
40
400
60
S
Stop Select
10
Text
➀
1
––
––
Ramp
Current Limit
36
%
1
20% of DRC
150% of Drive Rated Current (DRC)
150% of DRC
Overload Mode
37
Text
➀
1
––
––
No Derating
Overload Current
38
Amps
100 = DRC
20% of DRC
115% of Drive Rated Current (DRC)
115% of DRC
Sec Curr Limit
141
%
1
0
% of DRC
150% of Drive Rated Current (DRC)
0
% of DRC
Adaptive I Lim
149
Text
➀
1
––
––
Enabled
➀ Refer to Table B.6 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions