Frequency set group – Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual
Page 97

Programming
5-29
Frequency Set Group
(continued)
Table 5.A Frequency Source Selection
Parameter Settings
Frequency Source
➀
Accel/Decel
Control Terminal Block
Preset/
2nd
Accel(26)
Upper
Presets
(72)
Freq
Select 1
(5)
Freq
Select 2
(6)
Preset Freq 1
(27)
Preset Freq 2
(28)
Preset
Freq 3
(29)
Preset
Freq 4
(73)
Preset Freq 5
(74)
Preset
Freq 6
(75)
Preset Freq 7
(76)
Accel Time 1
(7)
Decel Time 1
(8)
Accel Time 2 (30)
Decel Time 2 (31)
SW3
TB2-18
SW2
TB2-17
SW1
TB2-16
•
•
•
0
0
0
•
•
•
0
0
X
•
•
•
0
X
0
Disabled
•
•
•
0
X
X
Disabled
➁
•
•
➂
•
➂
■
■
X
0
0
•
•
➂
•
➂
■
■
X
0
X
•
•
➂
•
➂
■
■
X
X
0
Preset
➁
•
•
➂
•
➂
■
■
X
X
X
➁
•
•
•
0
0
0
•
•
•
0
0
X
•
•
•
0
X
0
Enabled
•
•
•
0
X
X
Enabled
•
•
•
X
0
0
•
•
•
X
0
X
•
•
•
X
X
0
•
•
•
X
X
X
➀ The parameter [Freq Source] indicates the active frequency source. See p. 5-45.
➁ Factory default settings.
➂ Not valid for [Input Mode] = “3 W/2nd Acc” or [Input Mode] = “Run F/R 2nd A”.
■
Valid for [Input Mode] = “3 W/2nd Acc” or [Input Mode] = “Run F/R 2nd A”.
•
Indicates active function/parameter.
X
Indicates closed switch.
0
Indicates open switch.
(26) Indicates parameter number.