Serial Communications
B-4
Table B.3 Drive Status Data
This information will be displayed in the controller’s input image table when
the appropriate dip switch setting on the Communication Module is enabled.
Logic Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Status
Text
X
Enabled
1
= Enabled, 0 = Not Enabled
X
Running
1
= Running, 0 = Not Running
X
Command Direction 1
= Forward, 0 = Reverse
X
Rotating Direction
1
= Forward, 0 = Reverse
X
Accel
1
= Accelerating, 0 = Not
X
Decel
1
= Decelerating, 0 = Not
X
Alarm
1
= Alarm, 0 = No Alarm
X
Fault
1
= Faulted, 0 = Not Faulted
X
At Speed
1
= At Speed, 0 = NOT at Speed
X
X
X
Local
000
= TB2 Local
100
= Adapter 4 Local
001
= Adapter 1 Local
101
= Adapter 5 Local
010
= Adapter 2 Local
110
= Adapter 6 Local
011
= Adapter 3 Local
111
= No Local Control
X
X
X
X
Frequency
Reference
0000 = Freq Select 1
0001 = Preset Freq 1
0010 = Preset Freq 2
0011 = Preset Freq 3
0100 = Preset Freq 4
0101 = Preset Freq 5
0110 = Preset Freq 6
0111 = Preset Freq 7
1000 = Freq Select 2
1001 = Port 1 Adapter 1
1010 = Port 2 Adapter 2
1011 = Port 3 Adapter 3
1100 = Port 4 Adapter 4
1101 = Port 5 Adapter 5
1110 = Port 6 Adapter 6
1111 = Jog Frequency