Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual
Page 132

Troubleshooting and Fault Information
6-8
Table 6.B 1305 Fault Descriptions
(continued)
Fault Name & Number
Fault Description
Action to Take
Undervolt Fault
DC Bus voltage fell below the minimum value. [Line Loss
Monitor the incoming AC line for low voltage or line power
Undervolt Fault
F4
DC Bus voltage fell below the minimum value. [Line Loss
Fault] parameter is programmed to “U Volt Run”.
Monitor the incoming AC line for low voltage or line power
interruption.
UV Short Fault
F41
Excessive current has been detected between these two drive
output terminals.
Check the motor and external wiring to the drive output terminals
for a shorted condition.
UW Short Fault
F42
Excessive current has been detected between these two drive
output terminals.
Check the motor and external wiring to the drive output terminals
for a shorted condition.
VW Short Fault
F43
Excessive current has been detected between these two drive
output terminals.
Check the motor and external wiring to the drive output terminals
for a shorted condition.