Figure 4.8, Appears – Rockwell Automation 1203-EN1 EtherNet/IP-to-SCANport Module User Manual
Page 49

Configuring the Scanner or Bridge
4-5
Figure 4.8 Module Properties Dialog Box - Page 1
3. Edit the following information about the module:
4. Under Connection Parameters, edit the following:
The following table defines the number of 16-bit words that you need
for input and output depending on your configuration.
Table 4.A 1305 Drive (16-bit Reference/Feedback and Datalinks)
Box
Type
Name
A name to identify the module and drive.
Comm. Format Data - INT.
This setting formats the data in 16-bit words.
IP Address
The IP address of the module.
Box
Assembly Instance
Size
Input
1
(This value is required.)
The value will vary based on your
application (setting of Parameters 32 -
[SP I/O Cfg] and 46 - [M-S Output]).
Output
2
(This value is required.)
The value will vary based on your
application (setting of Parameters 32 -
[SP I/O Cfg] and 45 - [M-S Input]).
Configuration
6
(This value is required.)
0
(This value is required.)
Input
Size
Output
Size
Logic Command/
Status
Reference/
Feedback (16-bit)
Datalinks (16-bit)
A
B
C
D
4
2
✔
✔
6
4
✔
✔
✔
8
6
✔
✔
✔
✔
10
8
✔
✔
✔
✔
✔
12
10
✔
✔
✔
✔
✔
✔