Using Explicit Messaging
A Get Attribute Single message reads a single attribute value. In this
example, we read the value of a parameter in a 1305 drive.
Example Message Format
Figure 6.4 Message Format for a Get Attribute Single Message
The following table identifies key settings for the message format:
Example Get Attribute Single Message
Configuration
Value
Description
Refer to . . .
Service Type
(1)
Service Code
(1)
Class
Instance
Attribute
Destination
(1)
The default setting for Service Type is “Custom,” which enables you to enter a Service
Code that is not available from the Service Type pull-down menu. When you select a
Service Type other than “Custom” from the pull-down menu, an appropriate Hex. value
is automatically assigned to the service Code box which grays out (unavailable).
Get Attribute Single
e (Hex.)
f (Hex.)
74 (Dec.)
1 (Hex.)
ParameterReadValue
Read parameter data
Get Attribute Single
CIP Parameter Object
Parameter 74 - [Preset Freq 5]
Parameter Value
Controller tag for response data
—