Wire the connectors for the module channels – Rockwell Automation 1756-DHRIO ControlLogix Data Highway Plus-Remote I/O Communication Interface Module I.I. User Manual
Page 12

12 ControlLogix Data Highway Plus-Remote I/O Communication Interface Module
Publication
1756-IN003D-EN-P - July 2008
Wire the Connectors for the Module Channels
Data Highway +/Remote I/O Communications Connections
Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING
The local programming terminal port is intended for temporary use only and
must not be connected or disconnected unless the area is assured to be
nonhazardous.
If you connect or disconnect the communications connector with power applied
to this module or any device on the network, an electrical arc can occur. This
could cause an explosion in hazardous location installations.
8-pin mini DIN programming terminal
connection parallel to channel A when
channel A is configured for DH+
communication.
Pin Assignments for
8-Pin DIN Connectors
Pin no
Desc
1
Blue
3
Shield
6
Clear
Pin Assignments for Channel A
and B Connectors
DH+
Remote I/O
Pin no
Desc
Pin no
Desc
1
Clear
1
Blue
Shield
Shield
2
Blue
2
Clear
Wiring
Label
43238
Channel A and B
connectors