Rockwell Automation 1756-DHRIO ControlLogix Data Highway Plus-Remote I/O Communication Interface Module I.I. User Manual

Page 16

Advertising
background image

16 ControlLogix Data Highway Plus-Remote I/O Communication Interface Module

Publication

1756-IN003D-EN-P - July 2008

CNFG

FALT

Incorrect DH+ routing
table configuration.

Incorrect Data
Highway object
configuration.

Correct the configuration. Refer to the

1756-DHRIO User Manual, publication
1756-UM0514

.

Verify the module is inserted in correct slot.

Data Highway Plus

OK

Normal operation for
that channel.

None.

LINK

OFF

Channel B is disabled
because Channel A is
used for 230k DH+
operation.

None

Remote I/O

MUTE

LINK

No adapters found on
remote I/O.

Add an adapter to the remote I/O network.

RACK

OVER

Rack overlap on
remote I/O.

Reconfigure remote I/O racks.

DUPL

SCAN

Duplicate scanner on
remote I/O.

Check remote I/O adapter settings.

MAX_

DEV_

Maximum devices
exceeded on remote
I/O.

Remove devices to meet limitations on
remote I/O network.

CHAT

LINK

Babble detected on
remote I/O.

Check remote I/O device and network
connections.

OFF_

LINE

Not trying to
communicate.

None. Normal state if controller is not
controlling remote I/O.

OK

Normal operation

None.

Code

Description

Recommended Action

Advertising