CNFG
FALT
Incorrect DH+ routing 
table configuration.
Incorrect Data 
Highway object 
configuration.
Correct the configuration. Refer to the
.
Verify the module is inserted in correct slot.
Data Highway Plus
OK
Normal operation for 
that channel.
None.
LINK
OFF
Channel B is disabled 
because Channel A is 
used for 230k DH+ 
operation.
None
Remote I/O
MUTE
LINK
No adapters found on 
remote I/O.
Add an adapter to the remote I/O network.
RACK
OVER
Rack overlap on 
remote I/O.
Reconfigure remote I/O racks.
DUPL
SCAN
Duplicate scanner on 
remote I/O.
Check remote I/O adapter settings.
MAX_
DEV_
Maximum devices 
exceeded on remote 
I/O.
Remove devices to meet limitations on 
remote I/O network.
CHAT
LINK
Babble detected on 
remote I/O.
Check remote I/O device and network 
connections.
OFF_
LINE
Not trying to 
communicate.
None. Normal state if controller is not 
controlling remote I/O.
OK
Normal operation
None.
Code
Description
Recommended Action