Configure your 1756-dhrio module – Rockwell Automation 1756-DHRIO ControlLogix Data Highway Plus-Remote I/O Communication Interface Module I.I. User Manual

Page 18

Advertising
background image

18 ControlLogix Data Highway Plus-Remote I/O Communication Interface Module

Publication

1756-IN003D-EN-P - July 2008

Configure Your 1756-DHRIO Module

After installing your 1756-DHRIO module, you must configure it. For more
information, refer to the

Data Highway Plus-Remote I/O Communication

Interface Module User Manual, publication 1756-UM514

.

If the channel
A or B
indicator is

in this
channel mode

then the channel
status is

take this action

Off

All

Not on line.

Place channel on line.

Green

RIO scanner

Active RIO link. All
adapter modules are
present and not
faulted.

None, normal operation.

DH+

Operating.

None, normal operation.

Green
flashing

RIO scanner

One or more nodes
faulted or failed.

Check power at other
racks.

DH+

No other node on the
network.

Check cables.

Red

All

Hardware fault.

Reboot module. If red
reoccurs, replace module.

Red flashing

RIO scanner

Faulted adapters
detected.

Check cables.

Check power at other
racks.

DH+

Duplicate node
detected.

Check node address.

Advertising