Configure your 1756-dhrio module – Rockwell Automation 1756-DHRIO ControlLogix Data Highway Plus-Remote I/O Communication Interface Module I.I. User Manual
Page 18
 
18 ControlLogix Data Highway Plus-Remote I/O Communication Interface Module
Publication
1756-IN003D-EN-P - July 2008
Configure Your 1756-DHRIO Module
After installing your 1756-DHRIO module, you must configure it. For more 
information, refer to the 
If the channel 
A or B 
indicator is
in this 
channel mode
then the channel 
status is
take this action
Off
All
Not on line.
Place channel on line.
Green
RIO scanner
Active RIO link. All 
adapter modules are 
present and not 
faulted.
None, normal operation.
DH+
Operating.
None, normal operation.
Green 
flashing
RIO scanner
One or more nodes 
faulted or failed.
Check power at other 
racks.
DH+
No other node on the 
network.
Check cables.
Red
All
Hardware fault.
Reboot module. If red 
reoccurs, replace module.
Red flashing
RIO scanner
Faulted adapters 
detected.
Check cables.
Check power at other 
racks.
DH+
Duplicate node 
detected.
Check node address.