ControlLogix Data Highway Plus-Remote I/O Communication Interface Module 7

Publication

1756-IN003D-EN-P - July 2008

Set the Network Type and Node Address Switches

Before you install the module, you must set the network type switches for
each channel. If the network type is Data Highway Plus (DH+), you must also
set the node address switches for that channel to a unique address within the
range of 00-77.

IMPORTANT

If your module uses the 230k DH+ network, that is, Channel A switch set to 3,
Channel B is disabled.

Also, node address switches do not apply if you are using remote I/O.

Node Address Switches (behind cover)
Example shows channel A node
address at 10 and channel B node
address at 24.

Network Type Switches (behind cover)
Example shows channel A set for DH+
and channel B set for RIO.

Refer to the label
for switch settings.