Check Power Supply and Module Status
At powerup the module’s alphanumeric display begins a cycle through the
following sequences.
• Channel A and the network used for channel A - DH+ or RIO
• Channel A node address, if used for DH+
• Channel A status
• Channel B and the network used for channel B - DH+ or RIO
• Channel B node address, if used for DH+
• Channel B status
This sequence runs continuously during normal module operation.
IMPORTANT
For example, if your module uses the following:
•
Channel A for DH+ with node address 14
•
Channel B for RIO
and the channels are operating properly, you see the following sequence:
•
A DH, A#14, A OK, B IO, SCAN, B OK
CHA CHB
OK
H+/RIO
Alphanumeric status indicator illuminates and cycles through a
sequence of messages (described on page 15).
Power Supply indicator is green.
Module OK status indicator is
solid red, then flashing green.