Troubleshoot the power supply, Interpret the alphanumeric display – Rockwell Automation 1756-DHRIO ControlLogix Data Highway Plus-Remote I/O Communication Interface Module I.I. User Manual

Page 15

Advertising
background image

ControlLogix Data Highway Plus-Remote I/O Communication Interface Module 15

Publication

1756-IN003D-EN-P - July 2008

Troubleshoot the Power Supply

If the alphanumeric indicator on the 1756-DHRIO module does not cycle
through these messages on powerup, refer to the following table and to the
Troubleshooting section that follows.

Interpret the Alphanumeric Display

Your 1756-DHRIO module displays alphanumeric codes that provide
diagnostic information about your module. The alphanumeric display flashes
the codes at approximately 1 second intervals. The following table
summarizes the codes.

If the POWER
indicator is

Power Supply Status is

Recommended Action

Off

Not operating.

Turn power switch ON.

Check power wiring connections.

Check fuse.

On

Operating.

None, normal operation.

Code

Description

Recommended Action

Data Highway Plus

OFF

LINE

Data Highway Plus link
is in STOP state.

Correct the configuration.

Refer to the

1756-DHRIO User Manual,

publication 1756-UM0514

.

DUPL

NODE

Data Highway Plus
Duplicate node
address.

Choose another node address and reset
switches.

ONLY

NODE

Only node on Data
Highway Plus link.

Check the cables.