Rockwell Automation 1756-DHRIO ControlLogix Data Highway Plus-Remote I/O Communication Interface Module I.I. User Manual

Page 20

Advertising
background image

20 ControlLogix Data Highway Plus-Remote I/O Communication Interface Module

Publication

1756-IN003D-EN-P - July 2008

Environmental Specifications

Attribute

Value

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0…60 °C (32…140 °F)

Non-Operating
Temperature

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry
Heat),

IEC 60068-2-14 (Test Na, Unpackaged Non-operating
Thermal Shock):

-40…85 °C (-40…185 °F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

2 g @ 10…500 Hz

Operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Non-operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11:

Group 1, Class A

ESD Immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Advertising