Interpret the Status Indicators

The three status indicators on the module provide information about your
module and the status of each channel. The following tables outline the
indicator condition and the corresponding status, and explain what each
condition means.

If the Module OK
indicator is

Module Status

Recommended Action

Off

Not operating.

1.Apply chassis power.

2.Verify module is completely
inserted into chassis and
backplane.

Green flashing

Operating but not
routing messages and
no controller
transferring I/O.

None, if no messages are actively
being routed through the module and
no controller transferring I/O.

To route messages or transfer I/O, use
module default configuration or
configure module.

Red, then Off

Performing self-test.

None, normal operation.

Green

Operating and routing
messages.

None, normal operation.

Red

In major fault

Reboot module. If red reoccurs, then

replace module.

Red flashing

In major fault or
configuration fault.

Check alphanumeric indicator and
take action described in alphanumeric
display message table on page 15.